Favorite | Homepage | 简体中文
 

Phone:86-21-39876089

Fax:  86-21-39876318

Technology support:13774473636 

Business contact:13918410808

 

产品中心
Current transformer for GIS


Current transformer for GIS

Current transformer for GIS is installed inside of GIS. It provides current signals for secondary measuring instruments.

Reference standard: GB1208-2006 Current Transformer

Voltage class: 110Kv-500Kv

Primary current: 50A-5000A

Secondary current: 1A /5A

Rated short time thermal current: 40KA/3s 50KA/3s 63KA/3s

Profile dimension: As per customer request

Product structure: secondary winding is wounded around the annular core. The instrument transformer and the supporting shielding cylinder can be connected by casting soldering.

Product features:We use high quality raw materials and optimize calculation, thus the product provides higher precision and higher load while meeting all the constraint conditions.

Acceptance inspections:
1、 Visual inspection
2、 Terminal identification test
3、 Insulation resistance measurement
4、 Power frequency voltage withstand test for the secondary winding
5、 Polarity check
6、 Turn-to-turn Overvoltage Test
7、 Determination of accuracy and error
8、 Composite error determination
9、 Transient error determination(Only for transient transformer)

  Shanghai Zhenggang Electric Co. Ltd Copyright 2011-2014 Address:No. 6, Lane 6725, Beiqing Road, Qingpu District, Shanghai, ChinaPostcode:200233 Tel:021-39876089 Fax:021-39876318 Shanghai ICP No. 12011076